Defrosting Technology
1. Hot Air Defrosting
The high temperature refrigerant gas discharged from the refrigeration compressor is routed through an oil separator to remove excess oil before being introduced into the evaporator, where it melts the frost layer on the evaporator's exterior. After releasing heat, the hot working gas condenses into liquid and is discharged along with the accumulated oil in the evaporator into the drain bucket or low pressure circulation storage tank.
Advantages: Effective defrosting, short time, low labor intensity.
Scope of Application: Commonly used in general medium and small-sized refrigeration systems.
2. Spray Defrosting
A spray device is used to spray water to the surface of the evaporator to melt and wash away the frost layer by the heat of the water.
Advantages: Simple structure and easy maintenance
Scope of Application: Limited to defrosting of air coolers equipped with drain pipes, typically in cold storage environments where temperatures remain above -4°C.
3. Electric Defrosting
Air coolers employing electric defrosting are used, and electric heating elements are inserted into the evaporator coil. During defrosting, stop the operation of the air coolers and close the liquid supply valve. Then, turn on the power to the electric heating elements to defrost the air coolers. After the frost layer melts, turn off the power to the electric heating elements to defrost the air coolers. After the frost layer melts, turn off the power to the electric heating elements, start the compressor, open the liquid supply valve appropriately, and resume operation of the air coolers. This method consumes a significant amount of electricity and also causes large fluctuations in cold room temperature.
Advantages: Simple operation, easy implementation of automated control
Scope of Application: Small- and medium-sized Freon refrigeration systems
4. Defrosting during Shutdown
When the refrigeration equipment is not in operation, it can leave defrosting naturally.
Advantages: No auxiliary equipment required
Scope of Application: Test environments with a low frost layer thickness